Reactive power compensator – SMONE – 3 kVAR / SM-ASVG-3-0.4-4L-CW
Gross
Product details
Reactive power compensator SMone SM-ASVG-3-0.4-4L-CW
The three-phase SM-ASVG-3-0.4-4L-CW is an advanced reactive power compensator with a capacity of 3 kvar, designed for 0.4 kV installations. It effectively compensates reactive power, filters higher harmonics, and balances three-phase asymmetry, operating in a 3L + N + PE configuration. The device features an intuitive touchscreen and offers high efficiency exceeding 97%.
Key features of the SM-ASVG-3-0.4-4L-CW:
- Compensation of reactive power (both inductive and capacitive) to a set cos(φ), and balancing of three-phase asymmetry.
- Filtering of higher harmonics from the 2nd to the 50th harmonic.
- Total response time below 10 ms, providing a fast reaction to network changes.
- The neutral conductor’s capacity is 1.5 times that of the phase conductor for safe operation.
- Wide operating voltage range of 304–456 V AC and frequency 45–63 Hz.
- Multi-level overload, short-circuit, surge, and under/overvoltage protections.
Who is this a good choice for?
The SM-ASVG-3-0.4-4L-CW is an ideal solution for industrial sites, commercial facilities, and installations where reactive power, higher harmonics, or network asymmetry are problematic. Its versatile features and advanced protections make it a reliable tool for improving power quality and optimizing the performance of power systems.
| Parameter | SM-ASVG-3-0.4-4L-CW |
|---|---|
| Catalog number | 106067 |
| Application | reactive power compensation, higher harmonic filtering |
| Device parameters | |
| Rated voltage (V) | 400 (304-456) AC |
| Rated frequency (Hz) | 50 (45~63) |
| Compensation power (kvar) | 3 (inductive and capacitive reactive power) |
| Noise level (dB) | 38 |
| Compensation factor | >98% |
| Efficiency (%) | >97% |
| Connections, communication, display | |
| Mains connection (power conductors) | 3L+N+PE |
| Connection to network (current transformers) | serial: IN/OUT (Imax=63A, 40kW); parallel: IN |
| Digital outputs | 3 status signaling outputs (max. 20mA) |
| Digital inputs | 1 start input, 1 stop input |
| Communication | RS485 (Modbus), compatible with SM-OneHub |
| Display | built-in 4.3″ color touchscreen, ability to connect external 7″ HMI |
| Number of devices | no parallel connection possible |
| Functions | |
| Selectable functions | reactive power compensation to a set cos(φ), harmonic filtering, three-phase asymmetry balancing (various combinations) |
| Other technical parameters | |
| Transistor switching frequency (kHz) | 16 |
| Total response time (ms) | < 10 |
| Harmonic range | from 2 to 50 |
| Neutral conductor capacity | 1.5 times greater than the phase conductor |
| Protections, overload capability | |
| Protections | overload, short-circuit, surge, overvoltage and undervoltage, overheating, frequency variation, loss of supply |
| Overload capability | x1.1 for 1 h; x1.2 for 30 s |
| Mechanical and environmental parameters, standards compliance | |
| Ingress protection (IP) | IP20 |
| Altitude (m) | <2000 |
| Ambient operating temperature (°C) | -20~+50 (power reduction above 40°C) |
| Ambient humidity (%) | ≤90% (non-condensing) |
| Cooling method | Intelligent multi-stage active ventilation |
| Airflow through device (m³/h) | 55.2 – 60.7 (single fan); 165.6 – 182.1 (entire device) |
| Minimum cross-section of power conductors (mm²) | 2.5 |
| Recommended protection rating (A) | 6 |
| Dimensions (mm) | height 665, width 350, depth 90.5 |
| Weight (kg) | 18 |
| Installation method | Surface-mounted |
| Standards compliance | EN 50178:2018, EN IEC 61000-6-2:2009, EN IEC 61000-6-4:2019 |