Energy storage system – SOLAREDGE – CSS-OU-01-11-CA-197-01
Product details
CSS-OD
CSS-OD from SolarEdge is an energy storage system for grid-connected commercial and industrial facilities. It uses LFP cells, and the cabinet’s total capacity is 197.12 kWh, with a usable capacity of 187.15 kWh. It works with SolarEdge ONE for C&I, which optimizes energy production, storage, and consumption at the facility. The system requires an AC-coupled SolarEdge photovoltaic installation.
Key benefits of CSS-OD
- Flexible power configuration: one or two 50 kW inverters per cabinet; the maximum power with two inverters is limited to 98.5 kW. The system can be expanded to 4 MWh of capacity and up to 1 MW of active power.
- Optimizing energy use: support for increasing self-consumption, reducing peak power demand, tariff optimization, and energy export and import limits. Availability of some features depends on the region.
- Multi-level protection: protection at cell, module, module assembly and cabinet levels, thermal runaway detection and integrated fire detection and suppression mechanisms.
- Sensors and electrical protection devices: flood, door opening, temperature, humidity, CO and smoke detection, as well as protection against reverse polarity, ground faults, leakage currents and surges.
- Preparation for indoor and outdoor installation: factory-assembled and tested cabinet with an IP54 protection rating and a built-in HVAC system. SolarEdge Go software speeds up configuration and commissioning.
- 10-year system warranty: the performance warranty covers 8000 cycles or 10 years down to 70% SoH, in accordance with the manufacturer’s limited warranty terms.
Who is this a good choice for?
CSS-OD is designed for companies managing commercial and industrial facilities with an AC-coupled SolarEdge photovoltaic system. It meets the needs of users seeking to increase self-consumption, reduce peak power demand and manage energy based on tariffs. Expandable capacity and indoor or outdoor cabinet installation allow the configuration to be tailored to the facility’s needs.
| Parameter | CSS-OU-197 | PCS050 |
|---|---|---|
| Battery data | ||
| Cell chemistry | LFP | |
| Total battery capacity (kWh) | 197,12 | |
| Usable battery capacity (kWh) | 187,15 | |
| Total battery module capacity (kWh) | 17,92 | |
| Number of battery modules | 11 | |
| Maximum charge and discharge rate (C) | 0,5 | |
| DC voltage range (V) | 616 - 792 | |
| Auxiliary AC power supply | ||
| Supply voltage at 50 Hz (V) | 220+/-15% | |
| Supply voltage at 60 Hz (V) | 220+/-10% | |
| AC output data | ||
| Rated AC active power (kW) | 50 | |
| Maximum AC apparent power (kVA) | 55 | |
| Maximum continuous output current per phase (A) | 80 | |
| Rated line-to-line / phase voltage (V) | 400 / 230 | |
| AC output voltage range (V) | 340 – 440 | |
| AC frequency (Hz) | 50 / 60 ± 5 | |
| AC wiring layout | 3W + PE / 4W + PE | |
| Total harmonic distortion (%) | <3 | |
| Power factor range | -1 to 1 / leading, lagging | |
| Number of inverters per 197 kWh battery cabinet | 1 or 2 | |
| DC input data | ||
| Maximum DC input power (kW) | 55 | |
| Maximum DC current (A) | 55 x 2 | |
| Number of DC input interfaces | 2 | |
| Efficiency | ||
| Maximum inverter efficiency (%) | 97,5% | |
| Dimensions and weight | ||
| Dimensions W x D x H (mm) | 1300 x 1200 x 2360 | 650 x 324 x 715 |
| Weight (kg) | 2360 | 68 |
| Structure and installation | ||
| Protection rating | IP54 | IP65 |
| Corrosion protection class | C4 | |
| Cooling method | Built-in HVAC | Air Cooling |
| Noise level (dBA) | <70 | |
| AC input cable cross-section (mm²) | 25 to 35 mm² | |
| AC cable lug size | M6 | |
| Communication | ||
| Communication ports | RS-485 / CAN | |
| Operating conditions | ||
| Operating temperature (°C) | -30 to +50 (>45 derating) | -20 to +60 (>45 derating) |
| Power derating temperature threshold (°C) | >45 | |
| Operating humidity (%) | 5 to 95 (non-condensing) | |
| Maximum working height (m) | 3000 | |
| Safety | ||
| Temperature and humidity detection | Heat & humidity detectors | |
| Smoke detection | Photoelectric smoke detector | |
| Cabinet-level fire suppression | Cabinet level 2×aerosol + support external water pipe | |
| Fire suppression at battery module level | Energy Module integrated with NOVEC 1230 | |
| Reverse polarity protection | Yes | |
| Ground fault and leakage current detection | Earth fault and leakage fault detection | |
| Ground fault protection | Yes | |
| Leakage current protection | Yes | |
| DC surge protection | Yes | Type II integrated |
| AC surge protection | Yes | Type III integrated |
| Network monitoring | Yes | |
| Toxic gas detector | CO | |
| Emergency stop button | Integrated | |
| Flood sensor | Integrated | |
| Door opening sensor | Integrated | |
| Relief valves and explosion vent panels | integrated | |
| Certificates and standards | ||
| Safety standards | IEC 62619, including 7.3.3, UL9540A | IEC 62109-1, IEC 62109-2, IEC 62477-1 |
| Enclosure protection standard | IEC 60529 | |
| Electromagnetic compatibility standards | EN / IEC 61000-6-2, EN / IEC 61000-6-4 | IEC 61000-6-4, IEC 61000-3-11, EN/IEC 61000-3, CISPR 11 |
| Grid connection standards | NRS 097-2-1:2017 Edition 2.1, NRS 097-2-1:2024 Edition 3, CEI-016, CEI 0-21, VDE AR-N-4105, VDE AR-N 4110, EN 50549-1/10, RfG, NC RfG, PTPiREE, UNE 217002, NTS V2.1 | |
| Warranty | ||
| Product warranty (years) | 10 | |
The cabinet requires a single-phase power supply for the HVAC system. Noise was measured at a distance of 1 m for a cabinet with one inverter. Battery power may be limited in the range from -30 to -10 °C. The maximum power of inverters operating with the cabinet is limited to 98.5 kW.