Energy Meter – EASTRON – SDM630-Modbus V2

SKU: F280Z32 EAN: 2010000046005
Manufacturer

Net width

Net depth

Net height

Weight 0,38 kg
CN 90283019
Price 115,74 €
Incl. VAT

115,74 €
Incl. VAT

In stock:

1 pcs
Log in to place an order

115,74 €
Incl. VAT

In stock:

1 pcs
Log in to place an order

Product details

Manufacturer

Net width

Net depth

Net height

Weight 0,38 kg
CN 90283019

Eastron SDM630 Series

The series of advanced, multifunctional three-phase Eastron SDM630 energy meters is designed for DIN rail mounting and direct current measurement up to 100 A. These devices provide bidirectional measurement of electrical parameters, a high level of accuracy confirmed by MID B+D certification, and flexibility thanks to optional communication interfaces and pulse outputs. It is a reliable solution for comprehensive energy consumption monitoring in three-phase installations.

Key features of the Eastron SDM630 Series:

  • Direct measurement: Supports current up to 100 A at rated voltage 3×230/400 V AC.
  • MID certification: Compliance with Directive 2014/32/EU (MID certificate B+D) providing legal verification of measurements.
  • Versatile communication: Available variants with RS485 Modbus RTU interface, M-bus and configurable pulse outputs.
  • Bidirectional measurement: Comprehensive recording of active and reactive energy, including Import, Export and Net kWh.
  • Multi-parameter and multi-tariff: Monitoring of voltage, current, power, power factor, frequency and support for multiple tariffs in selected versions.
  • DIN rail mounting: Enclosure with IP51 protection rating intended for mounting in distribution switchboards.

Who is this a good choice for?

The Eastron SDM630 meter series is an ideal choice for installers, building managers and industrial and commercial consumers seeking precise, certified devices for sub-metering and energy monitoring. Thanks to extensive communication options (Modbus, M-bus) and the bidirectional measurement function, these meters are well suited for Energy Management Systems (EMS) and photovoltaic installations.

Parameter SDM630-Modbus SDM630-Mbus SDM630-MT SDM630-Std SDM630-Pulse SDM630-2T SDM630M-DI
Electrical specifications
Rated voltage Un (V AC) 3×230/400 V AC 3×230/400 V AC 3×230/400 V AC 3×230/400 V AC 3×230/400 V AC 3×230/400 V AC 3×230/400 V AC
Operating voltage range 80% – 120% Un 80% – 120% Un 80% – 120% Un 80% – 120% Un 80% – 120% Un 80% – 120% Un 80% – 120% Un
Base current Ib (A) 10 A 10 A 10 A 10 A 10 A 10 A 10 A
Maximum rated current Imax (A) 100 A 100 A 100 A 100 A 100 A 100 A 100 A
Operating current range 0,4% Ib – Imax 0,4% Ib – Imax 0,4% Ib – Imax 0,4% Ib – Imax 0,4% Ib – Imax 0,4% Ib – Imax 0,4% Ib – Imax
Overload withstand 30 Imax for 0.01 s 30 Imax for 0.01 s 30 Imax for 0.01 s 30 Imax for 0.01 s 30 Imax for 0.01 s 30 Imax for 0.01 s 30 Imax for 0.01 s
Operating frequency (Hz) 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Power consumption per phase ≤ 2 W / 10 VA ≤ 2 W / 10 VA ≤ 2 W / 10 VA ≤ 2 W / 10 VA ≤ 2 W / 10 VA ≤ 2 W / 10 VA ≤ 2 W / 10 VA
Connection configuration 3P4W / 3P3W / 1P2W 3P4W / 3P3W / 1P2W 3P4W / 3P3W / 1P2W 3P4W / 3P3W / 1P2W 3P4W / 3P3W / 1P2W 3P4W / 3P3W / 1P2W 3P4W / 3P3W / 1P2W
Accuracy and certification
Accuracy class Class 1 / Class B Class 1 / Class B Class 1 / Class B Class 1 / Class B Class 1 / Class B Class 1 / Class B Class 1 / Class B
MID certificate Yes (0120/SGS0151) Yes (0120/SGS0151) Yes (0120/SGS0151) Yes (0120/SGS0151) Yes (0120/SGS0151) Yes (0120/SGS0151) Yes (0120/SGS0151)
AC dielectric strength 4 kV for 1 min. 4 kV for 1 min. 4 kV for 1 min. 4 kV for 1 min. 4 kV for 1 min. 4 kV for 1 min. 4 kV for 1 min.
Impulse voltage withstand 6 kV (1.2 µs) 6 kV (1.2 µs) 6 kV (1.2 µs) 6 kV (1.2 µs) 6 kV (1.2 µs) 6 kV (1.2 µs) 6 kV (1.2 µs)
Standards compliance IEC 62053-21, EN50470-1/3 IEC 62053-21, EN50470-1/3 IEC 62053-21, EN50470-1/3 IEC 62053-21, EN50470-1/3 IEC 62053-21, EN50470-1/3 IEC 62053-21, EN50470-1/3 IEC 62053-21, EN50470-1/3
Communication and additional features
RS485 Modbus RTU port Yes No Yes Yes No Yes Yes
Modbus transmission speed (bps) 2400 – 38400 — 2400 – 38400 2400 – 38400 — 2400 – 38400 2400 – 38400
M-Bus port (EN13757-3) No Yes No No No No No
M-Bus transmission speed (bps) — 300 – 9600 — — — — —
Number of pulse outputs (pcs) 2 2 2 2 2 2 —
Pulse output type Passive Passive Passive Passive Passive Passive —
Pulse constant output 2 (imp/kWh) 400 imp/kWh 400 imp/kWh 400 imp/kWh 400 imp/kWh 400 imp/kWh 400 imp/kWh —
Pulse width (ms) 200 / 100 / 60 ms 200 / 100 / 60 ms 200 / 100 / 60 ms 200 / 100 / 60 ms 200 / 100 / 60 ms 200 / 100 / 60 ms —
Number of digital inputs (pcs) — — — — — — 2
Multi-tariff No No Yes (4 tariffs / 10 time zones) No No No No
Dual power supply No No No No No Yes No
Operating conditions and enclosure
Display LCD with backlight LCD with backlight LCD with backlight LCD with backlight LCD with backlight LCD with backlight LCD with backlight
Operating temperature (°C) -25°C to +55°C -25°C to +55°C -25°C to +55°C -25°C to +55°C -25°C to +55°C -25°C to +55°C -25°C to +55°C
Storage temperature (°C) -40°C to +70°C -40°C to +70°C -40°C to +70°C -40°C to +70°C -40°C to +70°C -40°C to +70°C -40°C to +70°C
Operating humidity (% RH) ≤ 90% (non-condensing) ≤ 90% (non-condensing) ≤ 90% (non-condensing) ≤ 90% (non-condensing) ≤ 90% (non-condensing) ≤ 90% (non-condensing) ≤ 90% (non-condensing)
Protection degree IP51 (indoor use) IP51 (indoor use) IP51 (indoor use) IP51 (indoor use) IP51 (indoor use) IP51 (indoor use) IP51 (indoor use)
Enclosure protection class II II II II II II II
Installation category CAT III CAT III CAT III CAT III CAT III CAT III CAT III
Pollution degree 2 2 2 2 2 2 2
Mechanical / electromagnetic environment M1 / E2 M1 / E2 M1 / E2 M1 / E2 M1 / E2 M1 / E2 M1 / E2
Dimensions (W × H × D) (mm) 72 × 100 × 66 72 × 100 × 66 72 × 100 × 66 72 × 100 × 66 72 × 100 × 66 72 × 100 × 66 72 × 100 × 66
Mounting DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm