Inverter – SOLAX – X3-ULT-15KP – hybrid – AFCI – HV
| Manufacturer | |
|---|---|
| Rated power | |
| Power supply | |
| Hybrid device | |
| Off-grid mode | |
| MPPT | |
| Warranty | |
| Net width | |
| Net depth | |
| Net height | |
| CAN | |
| CAN 2.0 | |
| RS485 | |
| SPD Type I | |
| SPD Type II | |
| SPD Type III | |
| SPD Type I+II | |
| SPD – Free slot | |
| AFCI | |
| MPPT voltage range | |
| Maximum input current per MPPT [A] | |
| Maximum input power [W] | |
| European efficiency | |
| Weight | 56,72 kg |
| CN | 85044086 |
Incl. VAT
Product details
| Manufacturer | |
|---|---|
| Rated power | |
| Power supply | |
| Hybrid device | |
| Off-grid mode | |
| MPPT | |
| Warranty | |
| Net width | |
| Net depth | |
| Net height | |
| CAN | |
| CAN 2.0 | |
| RS485 | |
| SPD Type I | |
| SPD Type II | |
| SPD Type III | |
| SPD Type I+II | |
| SPD – Free slot | |
| AFCI | |
| MPPT voltage range | |
| Maximum input current per MPPT [A] | |
| Maximum input power [W] | |
| European efficiency | |
| Weight | 56,72 kg |
| CN | 85044086 |
X3-ULTRA
X3-ULTRA is a series of three-phase transformerless inverters designed to work with photovoltaic installations and lithium-ion batteries. It supports grid-tied operation and EPS emergency power with a battery, with a switching time below 10 ms. Maximum efficiency reaches 98.0%, and MPPT tracking efficiency reaches 99.9%.
Main advantages of X3-ULTRA
- Rated AC apparent power 15–30 kVA and maximum DC input power 30–60 kW, depending on the model.
- 2–3 MPPT trackers, depending on the model, with two panel strings per MPPT and a voltage range of 160–950 V.
- Support for lithium-ion batteries with voltage 180–800 V and maximum charging/discharging current 60 A (2 × 30 A).
- EPS emergency power with battery: rated power 15–30 kVA depending on model, peak power equal to twice the rated power for 10 seconds, and switching time below 10 ms.
- Ingress protection IP66 and operating temperature range from −35 to +60°C, with power derating above +45°C.
- Electrical protections: anti-islanding protection, DC reverse polarity protection, AC short-circuit and overcurrent protection, overheat protection, and Type II surge protection on DC and AC sides.
Who is this a good choice for?
X3-ULTRA is aimed at owners of photovoltaic systems who want to combine grid-tied operation with the use of lithium-ion batteries. For users needing emergency power it provides an EPS output with a battery and switching below 10 ms. The rated AC apparent power range of 15–30 kVA allows selecting the variant matching the system power requirements.
| Parameter | X3-ULT-15KP | X3-ULT-15K | X3-ULT-20KP | X3-ULT-20K | X3-ULT-25K | X3-ULT-30K |
|---|---|---|---|---|---|---|
| DC Input | ||||||
| Maximum recommended panel power (Wp) | 30000 | 40000 | 50000 | 60000 | ||
| Maximum DC input power (W) | 30000 | 40000 | 50000 | 60000 | ||
| Maximum DC voltage (V) | 1000 | |||||
| Nominal DC operating voltage (V) | 600 | |||||
| Number of MPPT trackers / strings per MPPT | 3 (2 / 2 / 2) | 2 (2 / 2) | 3 (2 / 2 / 2) | 2 (2 / 2) | 3 (2 / 2 / 2) | |
| Maximum PV input current (A) | PV1: 36 / PV2: 36 | |||||
| Maximum PV short-circuit current (A) | PV1: 45 / PV2: 45 | |||||
| MPPT voltage range (V) | 160 – 950 | |||||
| Start-up voltage (V) | 200 | |||||
| AC Output (Grid-tied operation) | ||||||
| Rated AC power (VA) | 15000 (AS 4777 14999) | 20000 | 25000 | 30000 (AS 4777 29999) | ||
| Maximum AC apparent power (VA) | 16500 (AS 4777 14999) | 22000 | 27500 | 30000 (AS 4777 29999) | ||
| Rated grid voltage (V) | 3P4W, 400 / 230 | |||||
| Rated grid frequency (Hz) | 50 / 60 | |||||
| Rated AC current (A) | 21,8 | 29,0 | 36,3 | 43,5 | ||
| Maximum AC current (A) | 24,0 | 31,9 | 39,9 | 43,5 | ||
| Power factor | 1 (-0,8 ~ 0,8) | |||||
| AC current total harmonic distortion THDi (%) | < 3 | |||||
| AC Input | ||||||
| Rated AC power (VA) | 15000 | 20000 | 25000 | 30000 | ||
| Rated AC current (A) | 21,8 | 29,0 | 36,3 | 43,5 | ||
| Rated grid voltage (V) | 3P4W, 400 / 230 | |||||
| Rated grid frequency (Hz) | 50 / 60 | |||||
| Battery | ||||||
| Battery type | Lithium-ion | |||||
| Battery voltage range (V) | 180 – 800 | |||||
| Maximum charging / discharging current (A) | 60 (30 x 2) | |||||
| Emergency output EPS (with battery) | ||||||
| EPS peak power | 2 times rated power for 10 s | |||||
| Rated EPS power (VA) | 15000 | 20000 | 25000 | 30000 | ||
| Rated EPS voltage (V) | 400 / 230 | |||||
| EPS frequency (Hz) | 50 / 60 | |||||
| Rated EPS current (A) | 21,8 | 29,0 | 36,3 | 43,5 | ||
| Switching time (ms) | < 10 | |||||
| Output voltage total harmonic distortion THDv at linear load (%) | < 3 | |||||
| Power consumption | ||||||
| Night-time self-consumption (W) | < 5 | |||||
| Protections | ||||||
| Anti-islanding protection | YES | |||||
| DC reverse polarity protection | YES | |||||
| Insulation monitoring | YES | |||||
| Residual current monitoring | YES | |||||
| AC overcurrent protection | YES | |||||
| AC short-circuit protection | YES | |||||
| AC surge protection | YES | |||||
| Overheat protection | YES | |||||
| Reverse battery charging from grid | YES | |||||
| Surge protection | Type II, DC and AC | |||||
| Arc fault protection AFCI | Optional | |||||
| Efficiency | ||||||
| Maximum efficiency (%) | 98,0 | |||||
| European efficiency (%) | 97,7 | |||||
| Rated charging efficiency (%) | 98,5 / 97,0 | |||||
| MPPT tracking efficiency (%) | 99,9 | |||||
| Certifications and standards | ||||||
| Safety | EN / IEC62109 – 1 / – 2 | |||||
| Electromagnetic compatibility | EN61000 – 6 – 1 / 2 / 3 / 4, EN61000 – 3 – 11 / 12, EN 5011, IEC 62920 | |||||
| Certification | VDE4105 / G99 / AS4777 / EN50549 / CEI 0 – 21 / IEC61727 / PEA / MEA / NRS – 097 – 2 – 1 / RD1699 / TOR | |||||
| Operating conditions | ||||||
| Ingress protection | IP66 | |||||
| Operating temperature range (°C) | -35 ~ 60 (Derating above + 45) | |||||
| Relative humidity (%) | 0 ~ 100 | |||||
| Altitude above sea level (m) | < 3000 | |||||
| Storage temperature (°C) | -40 ~ +70 | |||||
| Dimensions and weight | ||||||
| Dimensions (width x height x depth) (mm) | 696 x 526 x 240 | |||||
| Weight (kg) | 47 | |||||
| General data | ||||||
| Cooling | Intelligent cooling | |||||
| Topology | Transformerless | |||||
| Communication | Modbus (RS485), Meter (RS485), DI x 5, DO x 2 | |||||
According to the note in the source, PV3 input is available only for models 15KP, 25K and 30K.