KEHUA BCS 1250K-B-HUD
Gross
Product details
Order lead time: 60/90 days
1500 Vdc Energy Storage Converter Series BCS-B-HUD (1250K-1725K)
The 1500 Vdc energy storage converters of the BCS-B-HUD series (models BCS1250K-B-HUD, BCS1500K-B-HUD, BCS1725K-B-HUD) are technologically advanced devices designed for large-scale energy storage applications. They feature a high level of safety with online insulation monitoring and adaptation to extreme environmental conditions. They offer intelligent functions such as support for parallel connection of multiple units, autonomous start-up, and strong grid adaptability, making them an ideal solution for a variety of uses, including smoothing the demand profile (reducing peak loads) and frequency modulation.
Key features of the BCS-B-HUD Energy Storage Converters:
- High power and efficiency: Rated power models from 1250 kW to 1725 kW (at 45°C), with a maximum PCS efficiency of up to 99%.
- Advanced safety features: Online insulation monitoring, adaptation to extreme conditions (high temperature, salt exposure, extreme cold), and integrated secondary circuit protection.
- Intelligent management and grid adaptability: Support for parallel connection of multiple units, autonomous start-up, H/LVRT (High/Low Voltage Ride Through) functionality providing strong grid adaptability and smooth startup.
- Versatile applications: Can be used for smoothing the demand profile (reducing peak loads), frequency modulation, connection to auxiliary grids for new energy systems, and more.
- Simple and efficient design: Effective layout that improves space utilization, integrated secondary circuit, unified metering, protection and communications, simplifying installation and operation.
- Wide operating range and resilience: Operating temperature from -35°C to +60°C, IP55 protection rating, intelligent forced-air cooling, and capability to operate at altitudes up to 4000 m.
Who is this a good choice for?
The BCS-B-HUD series energy storage converters are an ideal solution for operators of large-scale energy storage systems, energy project developers, and industrial enterprises seeking reliable and efficient equipment for large-scale energy management. Their advanced safety features, intelligent grid-adaptive capabilities, and versatile applications make them an excellent choice for grid stabilization, energy cost optimization, and integration of renewable energy sources. High efficiency and robustness in harsh conditions ensure long-term, effective operation.
| Item | BCS1250K-B-HUD | BCS1500K-B-HUD | BCS1725K-B-HUD |
|---|---|---|---|
| DC Input | |||
| Maximum DC voltage (Vdc) | 1500Vdc | 1500Vdc | 1500Vdc |
| DC voltage range (Vdc) | 1000-1500Vdc | 1000-1500Vdc | 1000-1500Vdc |
| Maximum DC current (A) | 1543A | 1683A | 1936A |
| Soft start | Yes | Yes | Yes |
| AC Output (to grid) | |||
| Rated usable AC power (kW@°C) | 1250kW@45°C | 1500kW@45°C | 1725kW@45°C |
| Maximum AC apparent power output (kVA) | 1375kVA | 1650kVA | 1897.5kVA |
| Rated grid voltage (Vac) | 690Vac 3P3W+PE | 690Vac 3P3W+PE | 690Vac 3P3W+PE |
| Grid voltage range (%) | -15%~10% (adjustable) | -15%~10% (adjustable) | -15%~10% (adjustable) |
| Grid frequency (Hz) | 50 Hz | 50 Hz | 50 Hz |
| Maximum output current (A) | 1266A | 1381A | 1588A |
| Power factor | >0.99 (at rated power) | >0.99 (at rated power) | >0.99 (at rated power) |
| Adjustable power factor | 1 (leading/advance)~1 (lagging) | 1 (leading/advance)~1 (lagging) | 1 (leading/advance)~1 (lagging) |
| THDI (%) | < 3% (at rated power) | < 3% (at rated power) | < 3% (at rated power) |
| AC Output (off-grid) | |||
| Rated AC output voltage (Vac) | 690Vac | 690Vac | 690Vac |
| Output voltage accuracy (%) | 1% | 1% | 1% |
| Maximum output current (A) | 1266A | 1381A | 1588A |
| THDu (%) | <3% (Obciążenie wkładki???) | <3% (Obciążenie wkładki???) | <3% (Obciążenie wkładki???) |
| Rated usable power frequency (Hz) | 50Hz/60Hz | 50Hz/60Hz | 50Hz/60Hz |
| Overload capacity (%) | 110% overload | 110% overload | 110% overload |
| PCS Efficiency/Performance | |||
| Maximum efficiency (%) | 99% | 99% | 99% |
| General data | |||
| Isolation mode | None | None | None |
| IP rating (protection degree) | IP55 | IP55 | IP55 |
| Operating temperature (°C) | -35°C~60°C (>45°C derating of rated values; reduction of allowable load) | -35°C~60°C (>45°C derating of rated values; reduction of allowable load) | -35°C~60°C (>45°C derating of rated values; reduction of allowable load) |
| Relative humidity (%) | 0~100% (no condensation) | 0~100% (no condensation) | 0~100% (no condensation) |
| Cooling type | Intelligent forced-air cooling | Intelligent forced-air cooling | Intelligent forced-air cooling |
| Dimensions (Width * Height x Depth) (mm) | 860x2270x1725mm | 860x2270x1725mm | 860x2270x1725mm |
| Weight (kg) | 1500 kg | 1500 kg | 1500 kg |
| Altitude (m) | 4000m (>2000m made per customer request) | 4000m (>2000m made per customer request) | 4000m (>2000m made per customer request) |
| Display | Touch screen | Touch screen | Touch screen |
| Communication protocol | Modbus-RTU, Modbus-TCP, IEC61850, IEC104 | Modbus-RTU, Modbus-TCP, IEC61850, IEC104 | Modbus-RTU, Modbus-TCP, IEC61850, IEC104 |
| Communication interface | RS485, Ethernet | RS485, Ethernet | RS485, Ethernet |
| Compliance with | IEC/EN 62477-1, EN IEC 61000-6-2/4, EN 50549-2, NC RfG, IEC 62116, IEC 61727 | IEC/EN 62477-1, EN IEC 61000-6-2/4, EN 50549-2, NC RfG, IEC 62116, IEC 61727 | IEC/EN 62477-1, EN IEC 61000-6-2/4, EN 50549-2, NC RfG, IEC 62116, IEC 61727 |
Notes:
- “Obciążenie wkładki???” in the THDu parameter requires verification or clarification, because the original text is unclear.