Reactive power compensator – SMONE – 5 kVAR / SM-ASVG-5-0.4-4L-CW

SKU: F30025 EAN: 2010000039700
Manufacturer

Net width

Net depth

Net height

CN 85044060
Price 1 605,57 
Gross

1 605,57 
Gross

In stock:

3 pcs
Login to place an order

1 605,57 
Gross

In stock:

3 pcs
Login to place an order

Karta katalogowa SMone SM-ASVG-5-0.4-4L-CW SMone-SM-ASVG-5-0.4-4L-CW-Karta-katalogowa.pdf Instrukcja obsługi SMone SM-ASVG-5-0.4-4L-CW SMone-SM-ASVG-5-0.4-4L-CW-Instrukcja-obslugi.pdf Deklaracja zgodności SMone SM-ASVG-5-0.4-4L-CW SMone-SM-ASVG-5-0.4-4L-CW-Deklaracja-zgodnosci.pdf

Product details

Manufacturer

Net width

Net depth

Net height

CN 85044060

Reactive power compensator SMone SM-ASVG-5-0.4-4L-CW

The active reactive power compensator SM-ASVG-5-0.4-4L-CW is a three-phase device designed for reactive power compensation and harmonic filtering in 0.4 kV installations. It delivers high efficiency and advanced energy management features.

Main features of the SM-ASVG-5-0.4-4L-CW:

  • Rated compensation power 5 kVAR (inductive and capacitive).
  • Wide nominal voltage range (304–456 V AC) and frequency range (45–63 Hz).
  • Advanced functions: reactive power compensation, harmonic filtering, correction of three-phase imbalance.
  • Fast response time under 10 ms thanks to a transistor switching frequency of 16 kHz.
  • Intuitive operation with a built-in 4.3″ color touchscreen.
  • Parallel operation of up to 8 units possible, with versatile communication options (RS485 Modbus).

Who is this a good choice for?

The device is an ideal solution for industrial and commercial sites facing issues with reactive power, higher harmonics, or three-phase imbalance. Its advanced features and ability to integrate with monitoring systems make it an effective option for optimizing electrical energy consumption.

Karta katalogowa SMone SM-ASVG-5-0.4-4L-CW SMone-SM-ASVG-5-0.4-4L-CW-Karta-katalogowa.pdf Instrukcja obsługi SMone SM-ASVG-5-0.4-4L-CW SMone-SM-ASVG-5-0.4-4L-CW-Instrukcja-obslugi.pdf Deklaracja zgodności SMone SM-ASVG-5-0.4-4L-CW SMone-SM-ASVG-5-0.4-4L-CW-Deklaracja-zgodnosci.pdf

Parameter SM-ASVG-5-0.4-4L-CW
Catalog number 106065
Intended use reactive power compensation, filtering of higher harmonics
Rated voltage (V) 400 (304-456) AC
Rated frequency (Hz) 50 (45-63)
Compensation power (kvar) 5 (reactive, both inductive and capacitive)
Noise level (dB) <40
Compensation ratio (%) >95
Efficiency (%) >97
Supply connection 3L+N+PE
Connection to supply (current measurement) series: IN/OUT (internal transformers, rated current Imax=60A, max connection power 40kW); parallel: IN (external transformers)
Digital outputs 3 outputs (operation status, ready, fault) – max. 20mA
Digital inputs 1 input (start), 1 input (stop)
Communication RS485 (Modbus), compatible with SM-OneHub module
Display built-in 4.3″ color touchscreen; support for external 7″ HMI panel
Number of devices (parallel operation) up to 8
Functions reactive power compensation to a target cos(φ), harmonic compensation, three-phase imbalance balancing, combinations of these
Transistor switching frequency (kHz) 16
Total response time (ms) <10
Harmonic range from 2 to 25
Neutral conductor capacity 1.5 times greater than a single phase conductor
Protections overload, short-circuit, surge, over- and under-voltage, overheating, protection against frequency changes, protection against loss of supply
Overload capacity x1.1 for 1 hour; x1.2 for 30 seconds
IP rating IP20
Altitude above sea level (m) <2000
Ambient operating temperature (°C) -20~+50 (with power reduction above 40°C)
Ambient humidity (%) ≤90 (non-condensing)
Cooling method Intelligent multi-stage active ventilation
Airflow through the device (m³/h) 75.1 – 82.2 (single fan); 224.4 – 247.2 (whole device)
Minimum cross-section of supply conductors (mm²) 2.5 (when connected with external transformers)
Recommended protection rating (A) 10 (when connected with external transformers)
Dimensions – height (mm) 510
Dimensions – width (mm) 350
Dimensions – depth (mm) 89
Installation method Surface-mounted
Compliance with standards EN 50178:2018, EN IEC 61000-6-2:2009, EN IEC 61000-6-4:2019

Official distribution