Energy Meter – EASTRON – SDM630-Modbus V2
Incl. VAT
Product details
Eastron SDM630 Series
The series of advanced, multifunctional three-phase Eastron SDM630 energy meters is designed for DIN rail mounting and direct current measurement up to 100 A. These devices provide bidirectional measurement of electrical parameters, a high level of accuracy confirmed by MID B+D certification, and flexibility thanks to optional communication interfaces and pulse outputs. It is a reliable solution for comprehensive energy consumption monitoring in three-phase installations.
Key features of the Eastron SDM630 Series:
- Direct measurement: Supports current up to 100 A at rated voltage 3×230/400 V AC.
- MID certification: Compliance with Directive 2014/32/EU (MID certificate B+D) providing legal verification of measurements.
- Versatile communication: Available variants with RS485 Modbus RTU interface, M-bus and configurable pulse outputs.
- Bidirectional measurement: Comprehensive recording of active and reactive energy, including Import, Export and Net kWh.
- Multi-parameter and multi-tariff: Monitoring of voltage, current, power, power factor, frequency and support for multiple tariffs in selected versions.
- DIN rail mounting: Enclosure with IP51 protection rating intended for mounting in distribution switchboards.
Who is this a good choice for?
The Eastron SDM630 meter series is an ideal choice for installers, building managers and industrial and commercial consumers seeking precise, certified devices for sub-metering and energy monitoring. Thanks to extensive communication options (Modbus, M-bus) and the bidirectional measurement function, these meters are well suited for Energy Management Systems (EMS) and photovoltaic installations.
| Parameter | SDM630-Modbus | SDM630-Mbus | SDM630-MT | SDM630-Std | SDM630-Pulse | SDM630-2T | SDM630M-DI |
|---|---|---|---|---|---|---|---|
| Electrical specifications | |||||||
| Rated voltage Un (V AC) | 3×230/400 V AC | 3×230/400 V AC | 3×230/400 V AC | 3×230/400 V AC | 3×230/400 V AC | 3×230/400 V AC | 3×230/400 V AC |
| Operating voltage range | 80% – 120% Un | 80% – 120% Un | 80% – 120% Un | 80% – 120% Un | 80% – 120% Un | 80% – 120% Un | 80% – 120% Un |
| Base current Ib (A) | 10 A | 10 A | 10 A | 10 A | 10 A | 10 A | 10 A |
| Maximum rated current Imax (A) | 100 A | 100 A | 100 A | 100 A | 100 A | 100 A | 100 A |
| Operating current range | 0,4% Ib – Imax | 0,4% Ib – Imax | 0,4% Ib – Imax | 0,4% Ib – Imax | 0,4% Ib – Imax | 0,4% Ib – Imax | 0,4% Ib – Imax |
| Overload withstand | 30 Imax for 0.01 s | 30 Imax for 0.01 s | 30 Imax for 0.01 s | 30 Imax for 0.01 s | 30 Imax for 0.01 s | 30 Imax for 0.01 s | 30 Imax for 0.01 s |
| Operating frequency (Hz) | 50 / 60 Hz | 50 / 60 Hz | 50 / 60 Hz | 50 / 60 Hz | 50 / 60 Hz | 50 / 60 Hz | 50 / 60 Hz |
| Power consumption per phase | ≤ 2 W / 10 VA | ≤ 2 W / 10 VA | ≤ 2 W / 10 VA | ≤ 2 W / 10 VA | ≤ 2 W / 10 VA | ≤ 2 W / 10 VA | ≤ 2 W / 10 VA |
| Connection configuration | 3P4W / 3P3W / 1P2W | 3P4W / 3P3W / 1P2W | 3P4W / 3P3W / 1P2W | 3P4W / 3P3W / 1P2W | 3P4W / 3P3W / 1P2W | 3P4W / 3P3W / 1P2W | 3P4W / 3P3W / 1P2W |
| Accuracy and certification | |||||||
| Accuracy class | Class 1 / Class B | Class 1 / Class B | Class 1 / Class B | Class 1 / Class B | Class 1 / Class B | Class 1 / Class B | Class 1 / Class B |
| MID certificate | Yes (0120/SGS0151) | Yes (0120/SGS0151) | Yes (0120/SGS0151) | Yes (0120/SGS0151) | Yes (0120/SGS0151) | Yes (0120/SGS0151) | Yes (0120/SGS0151) |
| AC dielectric strength | 4 kV for 1 min. | 4 kV for 1 min. | 4 kV for 1 min. | 4 kV for 1 min. | 4 kV for 1 min. | 4 kV for 1 min. | 4 kV for 1 min. |
| Impulse voltage withstand | 6 kV (1.2 µs) | 6 kV (1.2 µs) | 6 kV (1.2 µs) | 6 kV (1.2 µs) | 6 kV (1.2 µs) | 6 kV (1.2 µs) | 6 kV (1.2 µs) |
| Standards compliance | IEC 62053-21, EN50470-1/3 | IEC 62053-21, EN50470-1/3 | IEC 62053-21, EN50470-1/3 | IEC 62053-21, EN50470-1/3 | IEC 62053-21, EN50470-1/3 | IEC 62053-21, EN50470-1/3 | IEC 62053-21, EN50470-1/3 |
| Communication and additional features | |||||||
| RS485 Modbus RTU port | Yes | No | Yes | Yes | No | Yes | Yes |
| Modbus transmission speed (bps) | 2400 – 38400 | — | 2400 – 38400 | 2400 – 38400 | — | 2400 – 38400 | 2400 – 38400 |
| M-Bus port (EN13757-3) | No | Yes | No | No | No | No | No |
| M-Bus transmission speed (bps) | — | 300 – 9600 | — | — | — | — | — |
| Number of pulse outputs (pcs) | 2 | 2 | 2 | 2 | 2 | 2 | — |
| Pulse output type | Passive | Passive | Passive | Passive | Passive | Passive | — |
| Pulse constant output 2 (imp/kWh) | 400 imp/kWh | 400 imp/kWh | 400 imp/kWh | 400 imp/kWh | 400 imp/kWh | 400 imp/kWh | — |
| Pulse width (ms) | 200 / 100 / 60 ms | 200 / 100 / 60 ms | 200 / 100 / 60 ms | 200 / 100 / 60 ms | 200 / 100 / 60 ms | 200 / 100 / 60 ms | — |
| Number of digital inputs (pcs) | — | — | — | — | — | — | 2 |
| Multi-tariff | No | No | Yes (4 tariffs / 10 time zones) | No | No | No | No |
| Dual power supply | No | No | No | No | No | Yes | No |
| Operating conditions and enclosure | |||||||
| Display | LCD with backlight | LCD with backlight | LCD with backlight | LCD with backlight | LCD with backlight | LCD with backlight | LCD with backlight |
| Operating temperature (°C) | -25°C to +55°C | -25°C to +55°C | -25°C to +55°C | -25°C to +55°C | -25°C to +55°C | -25°C to +55°C | -25°C to +55°C |
| Storage temperature (°C) | -40°C to +70°C | -40°C to +70°C | -40°C to +70°C | -40°C to +70°C | -40°C to +70°C | -40°C to +70°C | -40°C to +70°C |
| Operating humidity (% RH) | ≤ 90% (non-condensing) | ≤ 90% (non-condensing) | ≤ 90% (non-condensing) | ≤ 90% (non-condensing) | ≤ 90% (non-condensing) | ≤ 90% (non-condensing) | ≤ 90% (non-condensing) |
| Protection degree | IP51 (indoor use) | IP51 (indoor use) | IP51 (indoor use) | IP51 (indoor use) | IP51 (indoor use) | IP51 (indoor use) | IP51 (indoor use) |
| Enclosure protection class | II | II | II | II | II | II | II |
| Installation category | CAT III | CAT III | CAT III | CAT III | CAT III | CAT III | CAT III |
| Pollution degree | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| Mechanical / electromagnetic environment | M1 / E2 | M1 / E2 | M1 / E2 | M1 / E2 | M1 / E2 | M1 / E2 | M1 / E2 |
| Dimensions (W × H × D) (mm) | 72 × 100 × 66 | 72 × 100 × 66 | 72 × 100 × 66 | 72 × 100 × 66 | 72 × 100 × 66 | 72 × 100 × 66 | 72 × 100 × 66 |
| Mounting | DIN rail 35 mm | DIN rail 35 mm | DIN rail 35 mm | DIN rail 35 mm | DIN rail 35 mm | DIN rail 35 mm | DIN rail 35 mm |