SOLAX AELIO-P50B100
| Manufacturer | |
|---|---|
| AFCI | |
| Net depth | |
| Maximum output current | |
| Rated power | |
| MPPT | |
| Capacity | |
| Charging current | |
| Discharge current | |
| Net width | |
| Net height | |
| Warranty | |
| CN | 85076000 | 
Gross
Product details
| Manufacturer | |
|---|---|
| AFCI | |
| Net depth | |
| Maximum output current | |
| Rated power | |
| MPPT | |
| Capacity | |
| Charging current | |
| Discharge current | |
| Net width | |
| Net height | |
| Warranty | |
| CN | 85076000 | 
Delivery time: 60/90 days
SolaX Power ESS-AELIO Hybrid ESS Cabinet
The SolaX Power ESS-AELIO hybrid cabinet is an advanced energy storage system designed for intelligent management and optimization of energy use in larger residential buildings and commercial applications. It combines a high-performance three-phase inverter (50 kW or 60 kW) with a large-capacity energy storage (up to 200 kWh per cabinet, expandable to the MWh range), offering reliability, safety, and flexible adaptation to a variety of needs.
Key features of the SolaX Power ESS-AELIO Hybrid ESS Cabinet:
- Intelligent energy management: Advanced algorithms based on artificial intelligence (AI) provide highly accurate state of charge (SOC) estimation, compatibility with virtual power plants (VPP) via SolaX Cloud and OpenADR, and Smart Schedule and Smart Scene functions to optimize energy consumption.
- High performance and scalability: Inverter power of 50 kW or 60 kW, battery cabinet capacity up to 200 kWh (LFP) with modular expansion possible to the MWh level, and an option to oversize PV input power up to 200%.
- Comprehensive safety and reliability: Four-level fire protection, high protection ratings (IP66 for the inverter, IP55 for the cabinet), integrated Type II surge protection (SPD) on both AC and DC sides, and optional arc fault protection (AFCI).
- Operational flexibility and adaptability: Capability to operate in on-grid and off-grid modes (emergency EPS power), support for unbalanced three-phase output, and a modular design with expandable capacity options for easy upgrades.
- Optimized photovoltaic performance: Global MPP scanning to maximize energy yield and support for up to 6 MPP trackers with a maximum input current of 40 A per tracker (depending on model), enabling efficient use of large PV installations.
Who is this a good choice for?
The SolaX Power ESS-AELIO hybrid cabinet is an excellent choice for owners of larger residential properties, small and medium-sized businesses, and other entities seeking a comprehensive and scalable energy management solution. With intelligent features, high performance, advanced protections, and the ability to operate both on-grid and off-grid, this system helps maximize self-consumption, ensure power continuity, and actively participate in modern energy systems such as virtual power plants (VPP).
| Parameter | AELIO-P50B100 (Cabinet) | AELIO-P50B200 (Cabinet) | AELIO-P60B100 (Cabinet) | AELIO-P60B200 (Cabinet) | X3-AELIO-49.9K (Inverter) | X3-AELIO-49.9K-P (Inverter) | X3-AELIO-50K (Inverter) | X3-AELIO-60K (Inverter) | X3-AELIO-61K (Inverter) | |
|---|---|---|---|---|---|---|---|---|---|---|
| DC SIDE (Cabinet) | ||||||||||
| Max. recommended PV array power (kWp) | 100 | 100 | 120 | 120 | ||||||
| Max. PV input voltage (V) | 1000 | |||||||||
| Start-up voltage (V) | 200 | |||||||||
| Nominal PV input voltage (V) | 650 | |||||||||
| MPPT voltage range (V) | 160 – 950 | |||||||||
| Number of MPP trackers / strings per MPP tracker | 5/2 | 5/2 | 6/2 | 6/2 | ||||||
| Max. input current per MPPT (A) | 40 | |||||||||
| PV array short-circuit current ISC per MPPT (A) | 50 | |||||||||
| AC SIDE (Cabinet) | ||||||||||
| Rated output power (kW) | 50 | 50 | 60 | 60 | ||||||
| Rated output current (A) | 72.2 | 72.2 | 86.6 | 86.6 | ||||||
| Max. apparent power (kVA) | 55 | 55 | 66 | 66 | ||||||
| Max. continuous output current (A) | 83.6 | 83.6 | 100.3 | 100.3 | ||||||
| Rated AC voltage (V) | 3/N/PE, 220/380 V; 3/N/PE, 230/400 V | |||||||||
| Rated AC frequency (Hz) | 50 Hz / 60 Hz | |||||||||
| Adjustable power factor range | -1 (0.8 lagging to 0.8 leading) | |||||||||
| THDi (rated power) (%) | < 3% | |||||||||
| BATTERY SIDE (Cabinet) | ||||||||||
| Battery type | LFP/280Ah | |||||||||
| Battery nominal capacity (kWh) | 100 | 200 | 100 | 200 | ||||||
| Battery nominal voltage (V) | 358.4 | 716.8 | 358.4 | 716.8 | ||||||
| Battery voltage range (V) | 280 – 408.8 | 560 – 817.6 | 280 – 408.8 | 560 – 817.6 | ||||||
| Rated charging/discharging current (A) | 140 | |||||||||
| Max. charging/discharging current (A) | 160 A (80 A × 2) | |||||||||
| GENERAL (Cabinet) | ||||||||||
| Dimensions (with inverter) (W × H × D) (mm) | 1310 × 2300 × 1140 | 2070 × 2420 × 1200 | 1310 × 2300 × 1140 | 2070 × 2420 × 1200 | ||||||
| Dimensions (without inverter) (W × H × D) (mm) | 1020 × 2300 × 1150 | 1680 × 2420 × 1200 | 1020 × 2300 × 1150 | 1680 × 2420 × 1200 | ||||||
| Weight (with inverter) (kg) | 1600 | 2800 | 1600 | 2800 | ||||||
| Weight (without inverter) (kg) | 1500 | 2700 | 1500 | 2700 | ||||||
| Operating ambient temperature range (°C) | -30 – 55°C | -30 – 50°C | -30 – 55°C | -30 – 50°C | ||||||
| Relative humidity (%) | 0 – 95% RH (non-condensing) | |||||||||
| Max. operating altitude (m) | 3000 | |||||||||
| Cooling concept | Intelligent air cooling | |||||||||
| Protection rating | Cabinet: IP55; Inverter: IP66 | |||||||||
| Fire protection | Aerosol (optional: Novec1230) / Water | |||||||||
| Topology | Non-isolated | |||||||||
| Standards | IEC62619, IEC63056:2000, IEC61000, IEC62477-1, UN38.3 | |||||||||
| AC INPUT AND OUTPUT (GRID) (Inverter) | ||||||||||
| Rated output power (kW) | 49.9 | 49.9 | 50 | 60 | 61 | |||||
| Rated output current (A) | 72.3 | 72.0 | 72.5 | 87.0 | 88.4 | |||||
| Max. apparent output power (kVA) | 49.9 | 49.9 | 55 | 66 | 66 | |||||
| Max. continuous output current (A) | 83.2 | 76.0 | 83.3 | 100.0 | 100.0 | |||||
| BATTERY (Inverter) | ||||||||||
| Battery type | Lithium | |||||||||
| Battery voltage range (V) | 180 – 820 | |||||||||
| Max. charging/discharging current (A) | 160 A (80 A × 2) | |||||||||
| EPS OUTPUT (OFF-GRID) (Inverter) | ||||||||||
| Rated EPS output voltage, frequency (V, Hz) | 230 / 400 V, 220 / 380 V, 50 Hz / 60 Hz | |||||||||
| Rated EPS output power (kVA) | 49.9 | 49.9 | 50.0 | 60.0 | 61.0 | |||||
| Peak EPS output power (kVA, s) | 75 kVA, 10s | 75 kVA, 10s | 55 kVA, Continuous | 66 kVA, Continuous | 66 kVA, Continuous | |||||
| EFFICIENCY (Inverter) | ||||||||||
| Max. efficiency (%) | 98.0% | |||||||||
| European efficiency (%) | 97.2% | |||||||||
| GENERAL (Inverter) | ||||||||||
| Net weight (kg) | < 100 | < 105 | < 100 | < 105 | < 105 | |||||
| Cooling concept | Intelligent air cooling | |||||||||
| Communication interfaces | RS485, CAN, pulse control, DI, DO | |||||||||
| Topology | Non-isolated | |||||||||
| Certificates and approvals | CE, VDE4105, G99, AS4777, EN50549, CEI 0-21, IEC61727, PEA/MEA, NRS-097-2-1, RD1699, TOR | |||||||||
| PROTECTION (Inverter) | ||||||||||
| Overvoltage/undervoltage protection | Yes | |||||||||
| DC isolation protection | Yes | |||||||||
| DC reverse polarity protection | Yes | |||||||||
| Grid monitoring | Yes | |||||||||
| DC injection monitoring | Yes | |||||||||
| Backfeed current monitoring | Yes | |||||||||
| Residual current detection | Yes | |||||||||
| Overtemperature protection | Yes | |||||||||
| Active anti-islanding method | Frequency shifting | |||||||||
| Surge protection (DC / AC) | DC: Type II, AC: Type II | |||||||||
| Arc fault circuit interrupter (AFCI) | Yes | |||||||||
| AC auxiliary power supply (APS) | Built-in | |||||||||
| HYBRID ESS CABINET SET (TB-HR140) | ||||||||||
| Battery type | LFP 280Ah | |||||||||
| Battery capacity (kWh) | 14.3 | |||||||||
| Battery configuration | 1P16S | |||||||||
| Battery nominal voltage (V) | 51.2 | |||||||||
| Battery voltage range (V) | 40 – 58.4 | |||||||||
| Weight (kg) | 115 | |||||||||
| Charge/discharge rate | ≤ 0.5 C | |||||||||
| Dimensions (W × H × D) (mm) | 461 x 228 × 778 | |||||||||
| Operating temperature range (°C) | -20 – 53°C | |||||||||
| Relative humidity (%) | 0 – 95% RH (non-condensing) | |||||||||
| Max. operating altitude (m) | 3000 | |||||||||
| Protection rating (IP) | IP20 | |||||||||
| Communication with PCS | CAN | |||||||||
Notes:
- ① The maximum input voltage is the upper limit of the DC voltage. Any DC input voltage above this may damage the inverter.
- ② Input voltage exceeding the MPPT voltage range may trigger inverter protection.
- ③ The ISC (short-circuit current) for a single PV input string is 35 A.